myDatalogC3e 3mA/6Rel

Output extension myDatalogC3e 3mA/6Rel

The extension module myDatalogC3e 3mA/6Rel is used for signal output of 3 mutually isolated mA (0/4…20 mA) outputs.
Furthermore, it offers 2 groups with a common root with 3 relays each. It is an output extension for devices of the myDatalogC3xx family .

Product features

  • 6x relay outputs for direct switching of loads
  • Relay outputs with max. 230V AC / 30V DC, 2.5kV rated surge voltage
  • 3x isolated mA outputs, galvanic isolation at extra-low voltage level
  • mA outputs with error detection (too high load or cable break)
  • Easy installation thanks to plug-in clamps
  • Compatible with all devices of the myDatalogC3xx family

Features:

  • CAN bus as system bus
  • 2x 3 relays with one common root each, contact as normally open with isolating links for 230VAC 3A (no optos)
  • 3x 0/4…20 mA outputs (galvanic isolation at extra-low voltage level)
  • Status LED for power supply, bus communication and relay status

Product configurator

You can use the runtime calculator to estimate both the autonomous runtime of the application and the associated costs. Actual costs and energy consumption depend on measurement conditions such as reception quality and ambient temperature. You can find detailed information on the tariffs here.

Technical data

myDatalogC3e 3mA/6Rel
Item no. 301112
Power supply 9...32VDC (+/-10% )
Power consumption typ. 5W (without sensors)
max. 9W (without sensors)
Housing
  • Material: Lexan/Noryl
  • Weight: 152g
  • Protection class: IP20/ IP40 (connection area / actuation area)
  • Dimensions (WHT): 70 x 92 x 57mm
Operating temperature -20...+60°C
Humidity 15...90%rH non-condensing
Storage temperature -40...+85°C
Outputs 6 x relays (2 groups for different potentials)
3 x analog output (active, galvanically isolated)

Relay Mode
  • Voltage AC: 230V
  • Voltage DC: 30V
  • Current DC: 3A / relay, 6A for common CC
  • Current AC: 3A / relay, 6A for common CC
  • Rated impulse voltage: 2.5kV
CAN interface 1 x CAN / CAN FD for communication with the myDatalogC3xx
Data transmission via CAN interface to the myDatalogC3xx
Product Document Category Revision Hardware Version
myDatalogC3e 3mA/6Rel Fact Sheet 03 current
myDatalogC3e 3mA/6Rel Manual 02 Hw 1.0
myDatalogC3e 3mA/6Rel
myDatalogC3e 12UI/2Rel
EU Declaration of Conformity 18.10.2023 from Hw 1.0
myDatalogC3e 3mA/6Rel 3D View Hw 1.0 from Hw 1.0
Voltage AC Voltage DC Current AC Current DC Rated surge voltage
Relay Mode 230V 30V 3A / relay
6A for common CC
3A / relay
6A for common CC
2.5kV

Which use case would you like to implement?