myDatalogC32x

Complete solution in the control cabinet

The myDatalogC32x is a complete package for telecontrol, automation and control tasks in the control cabinet.

PLC, router, firewall and data transmission to the web platform are already integrated in the unit. This means that process-related requirements are already solved and the integration effort of the solution is minimal.

Choice of ready-made IoT apps

Demo IoT apps are available for numerous applications in the Marketplace. Ready-made solutions are simply configured or adapted. The development of own IoT apps via the rapidM2M Studio is also possible.

Product configurator

Runtime Calculator

Starting Position Designed for permanent connection to the server (operating mode "Online"), measurement interval 1sec

Battery life in years

0
calculating...

Recommended tariff

calculating...
With the runtime calculator you can estimate the autonomous runtime of the application as well as the costs incurred. The actual costs and energy consumption depend on the measurement conditions, such as the reception quality and ambient temperature. Detailed information on the tariffs can be found here.

With the help of the runtime calculator, you can estimate the autonomous runtime of the application as well as the costs incurred. The actual costs and energy consumption depend on the measurement conditions, such as the reception quality and ambient temperature. Detailed information on the tariffs can be found here.

Product variations

ProducttitlemyDatalogC32x
Item no. C32x-301163-301164-301165-301293-301294
Power supply 9...32VDC
Data memory 3MB internal flash memory
Programming In Studio with C-like scripting language built on PAWN
Dimensions 70 x 92 x 63mm (without antenna)
Protection class IP20 / IP40 (connection area/operating area)
Operating temperature -20...+60°C
Inputs

3 x analogue or digital (individually configurable per channel)

  • 0...20mA / 4...20mA
  • 0...2V / 0...10V
  • PWM
  • Frequency
  • Digital / Counter

Resolution
  • 0...20mA / 4...20mA: 6,36µA
  • 0...2V: 610µV
  • 0...10V: 7,97mV
Outputs 2 x Relay (with parallel pulse relay for setpoint output to, for example, dosing pumps; each channel can be configured individually)
Serial interfaces

1 x RS485 (2-Leiter)

1 x CAN / CAN FD

1 x RS232 (4-Leiter)

Data transmission

Mobile radio optional:

  • 2G/M1/NB1 World
  • M1/NB1 EU
  • 3G World
  • 2G/4G EU
  • 2G/3G/4G World

SIM integrated SIM chip
Positioning by using GSM cell location
base price-
  

Do you want more infos about myDatalogC32x?

Stefan Pfeffer

To load the content, please click on the button. By doing so, you agree to the loading of HubSpot cookies. You can find out more in our privacy policy.

Load content

Request a quote for a device/application

Tell us about your application.
We will be happy to assemble the device according to your requirements.

To load the content, please click on the button. By doing so, you agree to the loading of HubSpot cookies. You can find out more in our privacy policy.

Load content

In order to use our live chat, you must agree to the loading of Hubspot cookies. You can find out more about this in our privacy policy.